Salt for Heating Boilers: Selection, Dosing and Maintenance
·1 min read
Why a boiler needs soft water
A 1 mm layer of scale raises gas consumption by 5-8%. At 3 mm it is already +15-20% gas and a real risk of overheating the heat exchanger. For boiler rooms, water treatment is not an option but a necessity.
How the system works
A softener (sodium cation exchange filter) is installed in front of the boiler. The resin captures calcium and magnesium and releases sodium. The resin is regenerated with a brine made from tablet salt.
Which salt to choose
Tablet salt (recommended)
- Even dissolution - stable brine concentration
- Does not form "bridges" in the brine tank
- Less maintenance
- Recommended by equipment manufacturers
Rock salt (acceptable)
- 20-30% cheaper
- Leaves sediment - more frequent cleaning
- Needs a larger brine tank
Consumption calculation
Formula: Q = V × K × 120 / 1000
Where: V - resin volume (l), K - regenerations per month, 120 - grams of salt per 1 l of resin.
| Boiler room type | Resin volume | Salt per month |
|---|---|---|
| Household boiler | 25 l | 12-18 kg |
| Small facility | 100 l | 48-96 kg |
| CHP plant / large facility | 500 l | 240-600 kg |
Maintenance schedule
- Weekly: check the salt level in the tank
- Monthly: test water hardness after the filter
- Every 3 months: inspect the tank, remove sediment
- Yearly: replace or regenerate the resin